| INPUT |
| Rated power |
10000 VA |
| Voltage |
380/400/415 Vac three-phase + N |
| Voltage tolerance |
± 20% |
| Frequency tolerance |
40/72 Hz |
| Power factor |
0.99 |
| BY PASS |
| Rated voltage |
380/400/415 Vac three-phase + N |
| Voltage tolerance |
± 15% (selectable from ± 5% to ± 25%) |
| Rated frequency |
50/60 Hz |
| Frequency tolerance |
± 5% (selectable from ± 0.25% to ± 10%) |
| Number phases |
3 + N |
| OUTPUT and INVERTER OUTPUT |
| Rated power |
10000 VA |
| Active power |
9000 W |
| Output current |
15 A |
| Number phases |
3 + N |
| Crest factor (Ipeak/Irms) |
3 : 1 |
| Waveform |
Sinewave |
| Static stability |
± 1% |
| Dynamic stability |
± 3% in 10 ms |
| Frequency |
50/60 Hz selectable |
| Voltage distortion with non-linear load |
3% |
| Voltage distortion with linear load |
1% |
| Overload |
125% 150% 168% of the rated current for 10' / 1' / 5" |
| BATTERIES |
| Type |
Maintenance-free sealed lead acid |
| Typical recharge time |
6 h |
| ENVIRONMENTAL |
| Color |
Dark grey RAL 7016 |
| Remote controls |
EPO and bypass |
| Communication |
Double RS232/C , slot for SNMP adapter and slot for voltage free contacts. |
| Safety compliance |
EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU |
| EMC compliance |
EN 62040-2 and Directive 2014/30/EU |
| Protection rating |
IP20 |
| AC/AC efficiency |
>94% |
| Line-Interactive/Smart Active efficiency |
>98% |
| Noise (at 1 m) |
<40 dBA at 1 m - Smart Active Mode |
| Remote signals |
voltage free contacts |
| Operating temperature |
0 ÷ 40 °C |
| Relative humidity |
95% no condensing |
| DATA |
| Weight |
305 kg |
| Dimensions (h w d) |
1320x440x850 mm |