PDF
RTF
Models MST 10
INPUT
Rated power 10000 VA
Voltage 380/400/415 Vac three-phase + N
Voltage tolerance ± 20%
Frequency tolerance 40/72 Hz
Power factor 0.99
BY PASS
Rated voltage 380/400/415 Vac three-phase + N
Voltage tolerance ± 15% (selectable from ± 5% to ± 25%)
Rated frequency 50/60 Hz
Frequency tolerance ± 5% (selectable from ± 0.25% to ± 10%)
Number phases 3 + N
OUTPUT and INVERTER OUTPUT
Rated power 10000 VA
Active power 9000 W
Output current 15 A
Number phases 3 + N
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Static stability ± 1%
Dynamic stability ± 3% in 10 ms
Frequency 50/60 Hz selectable
Voltage distortion with non-linear load 3%
Voltage distortion with linear load 1%
Overload 125% 150% 168% of the rated current for 10' / 1' / 5"
BATTERIES
Type Maintenance-free sealed lead acid
Typical recharge time 6 h
ENVIRONMENTAL
Color Dark grey RAL 7016
Remote controls EPO and bypass
Communication Double RS232/C , slot for SNMP adapter and slot for voltage free contacts.
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC compliance EN 62040-2 and Directive 2014/30/EU
Protection rating IP20
AC/AC efficiency >94%
Line-Interactive/Smart Active efficiency >98%
Noise (at 1 m) <40 dBA at 1 m - Smart Active Mode
Remote signals voltage free contacts
Operating temperature 0 ÷ 40 °C
Relative humidity 95% no condensing
DATA
Weight 305 kg
Dimensions (h w d) 1320x440x850 mm